Monokote Type Z-106
High Density
Cementitious Fireproofing
Monokote
Type Z-146 High Density Cementitious
Fire-proofing has been developed by
Grace Construction Prods. to meet
specialty, commercial and Industrial
fireproofing require-ments. Type Z-146
is a portland cement based, factory
mixed material requiring only the
addition of water on the job for
application. It is spray applied
directly to structural steel (beams &
columns), providing up to 4 hours of
fire resistance. Its physical
characteristics are excellent for areas
exposed to environmental of climatic
conditions. Also, Type Z-146 may be
used in areas where high durability is
required such as parking garages. Type
Z-146 is ideal for use in clean room
environments where issues such as
particle emissions and off gassing are
critical to the interior environment
within the building.
|
 |
|
Mokokote Z - 146 |
 |
Typical Uses & Applications
Monokote Type Z-106 is suitable for interior, exposed
Construction within:
|
 |
|
|
|
Features |
-
Factory Pre-Mixed
-
Non-Toxic
-
Attractive Finishes
-
Versatility
|
| |
 |
|
Physical Properties |
Recommended Specifications |
Test Method/Notes |
Laboratory Tested* Value |
|
Dry
Density |
Min.
640 kg/m3 (40 pcf) |
ASTM
E 605 |
See
Note Below*** |
|
Bond
Strength |
Min.
478 kN/m2 (10,000 psf) |
ASTM
E 736 (Modified)** |
609
kN/m2 (12,765 psf) |
|
Compressive Strength @ 10% Deformation |
3.79
MPa (550 psi) |
ASTM
E 761 |
4.08
MPa (592 psi) |
|
Hardness |
40 |
ASTM
D 2240 |
41 |
|
Yield |
- |
Theoretical Maximum |
1.55
m2 at 25mm (16.7 board feet) per bag |
|
Color |
- |
Natural Concrete Gray |
Black/White Available as Special Order |
|
Volatile Organic Content (off gassing) at 50°C
organic compounds C6-C28 |
Less
than 1 PPMW (Part Per Million by Weight) |
Dynamic Headspace (Thermal Dissorbtion Gas
Chromatography-Mass Spectrometry) |
Less
than 1 PPMW (Below Detectable Limits) |
|
Leachable Ammonia |
Less
than 50 PPB (50 Parts Per Billion, 50 Nanograms/mg) |
Leachable Ion by Ion Chromatography |
Less
than 50 PPB (Below Detectable Limits) |
*
Independent laboratory tested value, Report available
upon request.
** Modified to allow for high-density,
high-strength materials.
*** All in place performance tests should
be conducted at or below the minimum recommended
specification density. Tests reported here were
conducted at 632 kg/m3 (39.4 pcf)
|
 |
 |
 |
Because we understand your