Monokote Type Z-106  High Density Cementitious Fireproofing

Monokote Type Z-146 High Density Cementitious Fire-proofing has been developed by Grace Construction Prods. to meet specialty, commercial and Industrial fireproofing require-ments. Type Z-146 is a portland cement based, factory mixed material requiring only the addition of water on the job for application. It is spray applied directly to structural steel (beams & columns), providing up to 4 hours of fire resistance. Its physical characteristics are excellent for areas exposed to environmental of climatic conditions.  Also, Type Z-146 may be used in areas where high durability is required such as parking garages. Type Z-146 is ideal for use in clean room environments where issues such as particle emissions and off gassing are critical to the interior environment within the building.

Mokokote Z - 146

Typical Uses & Applications
Monokote Type Z-106 is suitable for interior, exposed Construction within:

  • Parking Garages

  • Exterior expo-sure

  • Mechanical rooms

  • Areas where a highly durable product is required

Features
  • Factory Pre-Mixed

  • Non-Toxic

  • Attractive Finishes

  • Versatility

 

Physical Properties

Recommended Specifications

Test Method/Notes

Laboratory Tested* Value

Dry Density

Min. 640 kg/m3 (40 pcf)

ASTM E 605

See Note Below***

Bond Strength

Min. 478 kN/m2 (10,000 psf)

ASTM E 736 (Modified)**

609 kN/m2 (12,765 psf)

Compressive Strength @ 10% Deformation

3.79 MPa (550 psi)

ASTM E 761

4.08 MPa (592 psi)

Hardness

40

ASTM D 2240

41

Yield

-

Theoretical Maximum

1.55 m2 at 25mm (16.7 board feet) per bag

Color

-

Natural Concrete Gray

Black/White Available as Special Order

Volatile Organic Content (off gassing) at 50°C organic compounds C6-C28

Less than 1 PPMW (Part Per Million by Weight)

Dynamic Headspace (Thermal Dissorbtion  Gas Chromatography-Mass Spectrometry)

Less than 1 PPMW (Below Detectable Limits)

Leachable Ammonia

Less than 50 PPB (50 Parts Per Billion, 50 Nanograms/mg)

Leachable Ion by Ion Chromatography

Less than 50 PPB (Below Detectable Limits)

*               Independent laboratory tested value, Report available upon request.  **             Modified to allow for high-density, high-strength materials.             ***            All in place performance tests should be conducted at or below the minimum recommended specification density.  Tests reported here were conducted at 632 kg/m3 (39.4 pcf)

Because we understand your business better.
 
 Other Services
 Technical inquiry
 FAQ
 Project Profile
 Thickness guide
 UL Classifications